Installation Prerequisites
JuiceBox requires one of the following to be installed by a qualified technician:
- NEMA 14-50 outlet
- Hardwired electrical connection
The JuiceBox power supply must be connected to a circuit breaker that is rated for at least 125% of the device's continuous load.
When selecting a location to install the outlet or hardwire connection, keep in mind that JuiceBox should be positioned:
- Within range of the local Wi-Fi network
- Within reach of the vehicle's charge port
- With sufficient vertical clearance:
- Mounted indoors: 24 - 48 in (61 - 122 cm) above the floor
- Mounted outdoors: 18 - 48 in (46 - 122 cm) above the ground
- Plug-In Version only: Within reach of the NEMA 14-50 outlet so that the cable does not strain. The cable is 1 foot (30 cm) long.
- If possible, sheltered from weather (away from direct sunlight and protected from rain)
Installation
Fully read and understand the directions before installation. Refer to additional safety information at the end of this document.
WARNING: Do not continue this installation until the circuit breaker is turned off.
Load Balancing
-
Only balance to the circuit level.
-
Only balance stations with the same specifications (Pro40 with Pro40).
-
Balancing specifications cannot exceed the rated continuous load of the circuit. (50 amp circuit = 40 amp continuous load allowed) (NEC 625.41 & 42) 2017 code.
-
Per NEC 625.42 additional outlets per circuit can be added due to the JuiceNet Automated Load Management System.