Installation Prerequisites
Overview
- NEMA 14-50 outlet
- Hardwired electrical connection
- The JuiceBox may require a disconnecting means if:
- Not within line of sight of the Electrical Panel
- Required by local code
- Hardwire version: Only the pre-installed, hard wire whip shall be used to connect to a junction box or disconnect. It is not long enough, nor is it meant to go directly into the electrical panel.
Location
When selecting a location to install the outlet or hardwire connection, keep in mind that JuiceBox should be positioned:
- Within range of the local Wi-Fi network
- Within reach of the vehicle's charge port
- Away from direct sunlight (for outdoor installation)
- Protected from rain (for outdoor installation)
- With sufficient vertical clearance:
- Mounted indoors: 24 - 48 in (61 - 122 cm) above the floor
- Mounted outdoors: 18 - 48 in (46 - 122 cm) above the ground
- Plug-In Version Only: Within reach of the NEMA 14-50 outlet so that the cable does not strain. The cable is 1 foot (30 cm) long.
Wiring And Circuit Requirements
32A | 40A | 80A | |
Output Power | 32A Max 7.7 kW at 240V 1-phase | 40A Max 9.6 kW at 240V 1-phase | 80A Max 19.2kW at 240V 1-phase |
Circuit Requirements |
40 Amp 2 pole breaker |
50 Amp 2 pole breaker |
100 Amp 2 pole breaker |
NOTE:
- For the installation wiring, please have your electrician size the conductors for both rated wire temperature and 125% continuous load. Please refer to both the National Electrical Code (NEC) and your local Authority Having Jurisdiction (AHJ) for any additional requirements.1
1The neutral wire is not used, but may need to be present in the receptacle.
Installation
Fully read and understand the directions before installation. Refer to important safety information at the end of this document.
This section describes installing the JuiceBox onto a wall mount. If installing onto a JuiceStand, refer to the JuiceStand Manual.
Load Balancing
-
Load balance to Circuit only.
-
Load balance to panel is NOT recommended.
-
Can only balance stations with the same specifications (Pro40 with Pro40).
-
Balancing specifications cannot exceed the rated continuous load of the circuit. (50 amp circuit = 40 amp continuous load allowed) (NEC 625.41 & 42) 2017 code.
-
Per NEC 625.42 additional outlets per circuit can be added due to the JuiceNet Automated Load Management System.
-
Recommend no more than 3 per circuit. The maximum number of stations per circuit is determined by dividing the number of continuous load amps allowed based on circuit size by 8. (e.g. 40 amps / 8 amps = 5 stations maximum). Note this may result in a slower charge per car.